VAV-PRC011M-EN 107
DDC Controls
Zone Occupancy Sensor
Sensor ships with 30-minute time delay pre-set from the factory. Time delay and sensitivity can be
field-adjusted.
Specifications
Power Supply
24 VAC or 24 VDC, ± 10%
Maximum VA Load
0.88 VA @ 24 VAC,
0.72 VA @ 24 VDC
Isolated Relay Rating
1 A @ 24 VAC or 24 VDC
Operating Temperature
32 to 131°F (0 to 55°C)
Storage Temperature
-22 to 176°F (-30 to 80°C)
Humidity Range
0 to 95% non-condensing
Effective Coverage Area
1200 sq ft
Effective Coverage Radius
22 feet
Housing Material
ABS Plastic
Dimensions
3.3" dia. x 2.2" deep (85 mm x 56 mm). Protrudes 0.36" (9 mm) from ceiling when installed.
The zone occupancy sensor is ideal for spaces with intermittent occupancy.
It is connected to the Trane DDC UCM and allows the zone to shift to
unoccupied setpoints for energy savings when movement is not detected
in the space.
The zone occupancy sensor has a multi-cell, multi-tier lens with a
maximum field of view of 360°. The maximum coverage area of the sensor
is 1200 square feet with a maximum radius of 22 feet from the sensor when
mounted at 8 feet above the floor.
Komentarze do niniejszej Instrukcji