104 VAV-PRC011M-EN
DDC Controls
Dimensions
DDC Zone Sensor
Specifications
Thermistor Resistance Rating
10,000 Ohms at 77°F (25°C)
Setpoint Resistance Rating
Setpoint potentiometer is calibrated to produce 500 Ohms at a setting of 70°F (21.11°C)
Electrical Connections
Terminal Block – Pressure Connections
Communications Jack – WE-616 (available for field installation)
Physical Dimensions
Width: 2.75" (69.85 mm)
Height: 4.5" (114.3 mm)
Depth: 1.0" (25.4 mm)
Receiver/Translator
Enclosure: Plastic
Height: 4.75" (120.6 mm)
Width: 2.90" (73.5 mm)
Depth: 1.08" (27.5 mm)
Sensor/Transmitter
Enclosure: Plastic
Height: 4.78" (121.4 mm)
Width: 2.90" (73.5 mm)
Depth: 1.08" (27.5 mm)
The DDC zone sensor is used in conjunction with the
Trane direct digital controller to sense the space
temperature and to allow for user adjustment of the
zone setpoint. Models with external zone setpoint
adjustments and occupied mode override
pushbuttons are available.