Trane Modular 20 to 35 Tons Instrukcja Instalacji Strona 17

  • Pobierz
  • Dodaj do moich podręczników
  • Drukuj
Przeglądanie stron 16
CXRC-SVX01F-EN 17
Installation - Electrical
General Electrical Recommendations
All wiring and disconnects must comply with local and
National Electrical Codes (NEC).The installer must provide
properly sized system interconnection and power supply
wiring with appropriate fused disconnect switches.
Electrical connection types, sizes, and locations are shown
in Figure 5, p. 10.SeeTable 7, p. 18 for electrical data
(MCA, MFS).This information is also provided on the unit
nameplate. Sample wiring diagrams are provided in this
manual.
Power Supply Wiring
Run appropriately sized power wiring and field-supplied
conduit through the line voltage access opening provided
on the front of the unit. See Figure 1, p. 6 for electrical
connection locations. Run wire and field supplied conduit
up to the conduit connection point located in the bottom of
the control panel. Make appropriate connections to the
power terminal block in the control panel. Install fused
disconnects as required by local codes. Provide proper
equipment ground to the ground connections in the
control panel.
System Interconnection Wiring
Run appropriately sized field supplied conduits, 115 and 24
volt control wiring through the 115 and 24 volt access
openings provided on the front of the unit. See Figure 5,
p. 10 for electrical connection locations. Run wire and field
supplied conduit to the conduit connection points
provided on the bottom of the control panel. Make
appropriate connections to the terminal blocks in the
control panel. Install safety devices if required by local
code. Provide proper equipment ground to the ground
connections in the control panel. See Table 7, p. 18 for
electrical data.
Unit Wiring Diagrams
Specific unit wiring diagrams are provided on the inside of
the control panel door. Use these diagrams for
connections or trouble analysis. See “Wiring Diagrams,
p. 27 for typical unit wiring diagrams.
Unit Voltage
Electrical power to the unit must meet stringent
requirements for the unit to operate properly.Total voltage
supply and voltage imbalance between phases must be
within the following tolerances as stated in the Voltage
Imbalance section of this chapter.
Voltage Supply
Measure each leg of supply voltage at the line voltage
disconnect switch. Readings must fall within voltage
utilization range shown on the unit nameplate. If voltage of
any leg does not fall within tolerance, notify the power
company to correct this situation before operating the
unit. Inadequate voltage to the unit can cause control
components to malfunction and shorten the life of relay
contacts and condenser fan motors.
Voltage Imbalance
Excessive voltage imbalance between phases in a three-
phase system can cause motors to overheat and
eventually fail. Maximum allowable imbalance is 2%.
Voltage imbalance is defined as 100 times the maximum
deviation of the three voltages (three phases) subtracted
from the average (without regard to sign) divided by the
average voltage.
WARNING
Hazardous Service Procedures!
The maintenance and troubleshooting procedures
recommended in this section of the manual could result
in exposure to electrical, mechanical or other potential
safety hazards. Always refer to the safety warnings
provided throughout this section concerning these
procedures. Unless specified otherwise, disconnect all
electrical power including remote disconnect and
discharge all energy storing devices such as capacitors
before servicing. Follow proper lockout/tagout
procedures to ensure the power can not be
inadvertently energized. When necessary to work with
live electrical components, have a qualified licensed
electrician or other individual who has been trained in
handling live electrical components perform these
tasks. Failure to follow all of the recommended safety
warnings provided, could result in death or serious
injury.
NOTICE:
Use Copper Conductors Only!
Unit terminals are not designed to accept other types of
conductors. Failure to use copper conductors could
result in equipment damage.
WARNING
Live Electrical Components!
During installation, testing, servicing and
troubleshooting of this product, it may be necessary to
work with live electrical components. Have a qualified
licensed electrician or other individual who has been
properly trained in handling live electrical components
perform these tasks. Failure to follow all electrical
safety precautions when exposed to live electrical
components could result in death or serious injury.
NOTICE:
Motor Damage!
Correct phase sequence is critical. Incorrect phase
sequence of the incoming line voltage could result in
motor damage.
Przeglądanie stron 16
1 2 ... 12 13 14 15 16 17 18 19 20 21 22 ... 27 28

Komentarze do niniejszej Instrukcji

Brak uwag