VRF-SVN33A-EN 9
Preparing for Installation
circulation. Consult an installation expert about taking anti-corrosion measures, such as
removing salinity on the heat exchanger and applying a rust inhibitor more frequently
than once a year.
– At least 9.84 ft (3 m) away from equipment that generates electromagnetic waves.
– Away from interfering sources, such as radio, computer, and stereo equipment.
– Far enough away from people living and working nearby so that hot discharge air or noise
do not disturb them.
– Away from inflammable materials.
• Ensure that condensate water generated by the outdoor unit can drain smoothly away from the
unit.
• Install the power and communication cables in a separately installed enclosure.
• If installing on a high place such as a roof, with a fence or guard rail around it.
• If there is a potential for accumulated snow to block the air inlet or heat exchanger, install the
unit on a higher base.
• R-410A refrigerant is a safe, nontoxic and nonflammable refrigerant. However, if there is a
concern about a dangerous level of refrigerant concentration in the case of refrigerant leakage,
add extra ventilation.
• Avoid installing the outdoor unit where corrosive gases, such as sulfur oxides, ammonia, and
sulfurous gas, are produced. If unavoidable, consult with an installation specialist about using
a corrosion-proof or anti-rust additive to protect the unit coils.
Moving the Mini Outdoor Unit
Follow these guidelines when moving the mini outdoor unit:
• Before moving the unit, determine a path that can support its weight.
• Do not lay the unit on its side and do not slant the unit more than 30 degrees.
• Take care to avoid injury while moving the unit; the surface of the heat exchanger is sharp.
– If moving the unit with a crane, fasten the wire rope as shown in Figure 4. To protect damage
or scratches to the unit, use a spreader bar.
– If the unit is being moved a short distance by hand, two people should lift and carry it
together using the transportation handles on the side of the unit, as shown in Figure 4.
ODU
Sea breeze
Sea breeze
Sea
Sea
Sea
Sea breeze
ODU
ODU
ODU
ODU
Protection walls