40 VRF-SVN33A-EN
Control System
Table 21. System configuration using DIP switches K13–K16
DIP switch
Maximum current per unit model
4TVH0036B100NB
3 ton
4TVH0048B100NB
4 ton
4TVH0053B100NB
5 ton
Current limit option
K13 On
Maximum current default: 22 A Maximum current default: 24 A Maximum current default: 32 A
K14 On
K13 On
Default – 4 A Default – 2 A Default – 2 A
K14 Off
K13 Off
Default – 6 A Default – 4 A Default – 4 A
K14 On
K13 Off
Default – 8 A Default – 6 A Default – 6 A
K14 Off
Defrost optimization
(a),(b),(c)
(a) This option is used in locations where humidity is high and, as a result, defrost mode occurs frequently.
(b) Maintaining factory default status is recommended. If set to Low, the temperature at which it enters defrost mode will
decrease. If the temperature at which it enters defrost mode decreases, the duration of defrost operation will increase. As
a result, the overall heating capacity will be reduced.
(c) Defrost mode will start when the difference between the outdoor temperature and the outdoor coil temperature has
exceeded its t.
K15 On
Default: Mid
K16 On
K15 On
Default: Mid
K16 Off
K15 Off
Low1
K16 On
K15 Off
Low2
K16 Off