VAV-SVX02B-EN
Reversing Relay
Calibration
By using the “bias” adjustment on the
relay, the factory-set 8.09.0 “cross-
over” can be changed. To recalibrate,
the relay should be connected as
illustrated in Figure 8.
Figure 8Recalibrating Reversing Relay
If the new desired “cross-over”
pressure is 11.0 psi, this must be applied
to port #3 by adjusting the pressure
regulator. The “bias” adjustment is then
turned until 11.0 psi is obtained on the
output gage. Turning the “bias” adjust-
ment “CW” increases the output;
“CCW” decreases it.
This 11.0 psi “cross-over” would yield
the following operational chart:
Specifications
Maximum Pressure:
30 psig
Connections:
3/16" (4.& mm) nipples for ¼" (6.4 mm) OD
polyethylene tubing
Air Consumption:
0.5 SCFH (.236 L/M) @ 20 psig
Material:
ABS
Weight:
3 ½ oz
Chart
Input: 1234567891011121314151617181920
Output: 2019181716151413121110987654321
New Cross-over pressure
Bias
Adjustment
Screw
Gage
M
1
C
3
M
Pressure
Regulator
Ambient Limits:
+40°F/+120°F operating (+4°C/+49°C)
Mounting:
In-line via air connections
Factory Settings:
9 psig in./9 psig out and 8 psig in./8 psig
out
Bias Adjustment:
+/-15 psi