Wiring requirements and options
CNT-SVX07C-EN 27
Figure 11. Four-pipe heating/cooling unit with auto changeover
LonTalk
in
Outdoor air or
generic temperature
24 V
Exhaust (or fan, medium speed)
24 V
Fan, low speed
24 V
Fan, high speed
Low-coil-temperature detection
(closed=normal)*
Condensate overflow (closed=normal)*
Occupancy (open=occupied)*
LonTalk
H
N
24 Vac
24 V
Generic/baseboard heat
24 V
Heating/cooling changeover valve
out
Fan status (closed=on)*
24 V
Outdoor air damper actuator
Discharge air
temperature
24 V
Auxiliary heating valve
Open
Close
Open
Close
Entering water
temperature
Open
Close
* All binary inputs are configurable.
Connect 24 V to an AC POWER (24V) terminal.
AI4 input: See
Figures 5 and 6
on page 20 for
wiring options