SAFETY WARNINGOnly qualified personnel should install and service the equipment. The installation, starting up, and servicing of heating, ventilating,
10 VRF-SVX30A-ENInstallationInstalling Refrigerant PipingConnect field-supplied piping using flared connections (not supplied) or by brazing. The lar
VRF-SVX30A-EN 11Installation3. Attach the yoke to the flaring bar, centering the conical part over the end of the pipe that is extending above the fla
12 VRF-SVX30A-ENInstallationLeak Testing Pipe Connections Notes:• All required piping pressure tests must be completed in accordance with national an
VRF-SVX30A-EN 13InstallationInstalling the Drain SystemFollow these precautions and recommendations when installing the drain hose to the indoor unit:
14 VRF-SVX30A-ENInstallation5. Pass the drain hose under the refrigerant pipe and through the hole in the wall. Keep the hose tight and make sure it
VRF-SVX30A-EN 15InsulationInsulationAfter determining that there are no leaks in the refrigerant pipes or drainage hose, insulate them as described in
16 VRF-SVX30A-ENWiring the UnitWiring the UnitObserve the following precautions when making electrical connections. • Make all electrical connections
VRF-SVX30A-EN 17Wiring the UnitFigure 1. Wiring diagram1(L)2(N) F2F1 1(L)1(L)2(N)2(N)F1F1F2F2F4F3F3 F4208–230 VF1F2NLNLNLNLF1F2F1F1F1F2F2 F21(L)2(N)
18 VRF-SVX30A-ENConfigurationConfigurationAll VRF indoor units are factory configured. If modifications are required, one of the following control de
VRF-SVX30A-EN 19ConfigurationFigure 2. VRF Wireless Remote ControlMode buttonFan upTemp upTemp downFan downPower button2-digit segment
© 2013 Trane All rights reserved VRF-SVX30A-ENIntroductionRead this manual thoroughly before operating or servicing this unit.Warnings, Cautions, a
20 VRF-SVX30A-ENConfigurationThe 2-Digit SegmentsEach 2-digit segment is differentiated from the others by a combination of operation mode and timer
VRF-SVX30A-EN 21ConfigurationMode 2: Option SettingWhen digit 2 is set to a value of “2,” the options shown in Table 1 can be set to the values in the
22 VRF-SVX30A-ENConfiguration14 External control0: Disabled1: On/Off control2: Off-only control15 External control output0: Thermostat control1: User
VRF-SVX30A-EN 23ConfigurationMode 5: Option SettingWhen digit 2 is set to a value of “5,” the options shown in Table 2 can be changed to the values in
24 VRF-SVX30A-ENConfigurationFigure 5. Heat recovery unit operating in auto-changeover mode9Time required for mode changeNote: Applies only when digi
VRF-SVX30A-EN 25ConfigurationMode A: AddressingWhen digit 2 is set to a value of “A,” unit address settings can be changed. See Figure 7, Figure 8, an
26 VRF-SVX30A-ENConfigurationMode d: Specific Digit ChangingWhen digit 2 is set to a value of “d,” a single, specific digit can be changed. See Figur
VRF-SVX30A-EN 27ConfigurationFigure 9. Example of using the specific digit changing mode to change an option settingThe example in Figure 11 shows how
28 VRF-SVX30A-ENConfigurationTable 4. Specific digit changing mode: Digit 2 = dDisplay screen (Mode and On/Off)DigitOption Set digit to...1 Factory s
VRF-SVX30A-EN 29OperationOperationFamiliarize yourself with the unit components and operating tips before operating the unit.ComponentsNote: Your unit
Table of ContentsVRF-SVX30A-EN 3Introduction . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
30 VRF-SVX30A-ENOperationInternal ProtectionsInternal protections operate if an internal fault occurs in the unit. Note: If the heat pump is operatin
VRF-SVX30A-EN 31Operation2. Hold on to the handle and lift it up. Remove the filter by pulling it towards you.3. Clean the air filter with a vacuum or
32 VRF-SVX30A-ENTroubleshootingTroubleshootingRefer to Table 6 for solutions to common problems and to Table 7 for a list of alarm conditions with co
VRF-SVX30A-EN 33TroubleshootingIf an error occurs, one of more of the LEDs on the display (see “Components” for their location) will flicker. As a pro
34 VRF-SVX30A-ENTroubleshootingCondenser mid-sensor is loose E241On Flickering FlickeringRefrigerant leakage (2nd detection) E554Abnormally high temp
VRF-SVX30A-EN 35Warranty For Trane Advantage™ VRF Systems and Related AccessoriesWarranty For Trane Advantage™ VRF Systems and Related AccessoriesProd
36 VRF-SVX30A-EN
The manufacturer optimizes the performance of homes and buildings around the world. A business of IngersollRand, the leader in creating and sustaining
4 VRF-SVX30A-ENTroubleshooting . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 32Warra
VRF-SVX30A-EN 5Model Number DescriptionDigit 1: RefrigerantDigit 2: Brand name Digit 3: System typeDigit 4: Configuration Type (also see separate tab)
6 VRF-SVX30A-ENPreparing for InstallationPreparing for InstallationAccessoriesIn addition to product literature, the following accessories are suppli
VRF-SVX30A-EN 7Preparing for InstallationService Clearances 11.81 in. (300 mm)4.9 in. (125 mm)4.9 in. (125 mm)
8 VRF-SVX30A-ENInstallationInstallationReview “Installation Considerations” before proceeding with installation.Follow the procedures in these sectio
VRF-SVX30A-EN 9InstallationPurging the UnitThe unit is shipped from the factory with a holding charge of nitrogen. All of this gas must be purged from